Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Electromagnetic |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Type | HSM2-2A | HSM2-4A | HSM2X-4A | |||
Standards | IEC/EN 61009-1, IEC/EN 61009-2-1; | |||||
Certificate | KEMA KEUR, CB, CE, UKCA, RoHS | |||||
Country of origin | CHINA | |||||
Electrical features | Type (wave form of the earth leakage sensed) | Type A, Type A[S], Type A[G] Type AC |
||||
Number of poles | 1P+N | 3P+N | ||||
Rated current | In | A | 6, 10, 13, 16, 20, 25, 32, 40, 50, 63 A | 6, 10, 13, 16, 20, 25, 32, 40 A | 50, 63 A | |
Rated sensitivity | IΔn | mA | 10, 30, 100, 300 mA | 30, 100, 300 mA | 30, 100, 300 mA | |
Rated voltage | Ue | V | 220/230/240 V | 380/400/415 V | 380/400/415 V | |
Operating time | Type A / Type AC | Instantaneous | Instantaneous | Instantaneous | ||
Type A[S] | - | - | 10 ms delay | |||
Type A[G] | - | - | 40 ms delay | |||
Insulation voltage | Ui | V | 500V AC | |||
Overvoltage category | III | |||||
Pollution degree | 2 | |||||
Operating voltage of circuit test | V | 187 - 264 V | 230 - 485 V | 230 - 485 V | ||
Rated frequency | Hz | 50/60 Hz | ||||
Rated breaking capacity acc. to IEC/EN 61009-1 | Icn | A | 6,000 A | |||
Rated breaking capacity acc. to IEC/EN 64947-2 (Only referring to short circuit test) |
Icu | A | 10,000 A | |||
Ics | A | 5,000 A (50%Icu) | ||||
Rated residual breaking capacity acc.to IEC/EN 61009-1 |
IΔm | A | 3000 A | |||
Rated impulse withstand voltage (1.2/50) | Uimp | kV | 4 kV | |||
Dielectric test voltage at ind. freq. for 1 min. | kV | 2.5 kV (50/60Hz, 1 min.) | ||||
Thermomagnetic release - characteristics | Characteristics B: 3In - 5In | |||||
Characteristics C: 5In - 10In | ||||||
Energy limiting class acc. to EN 61009-1 | 3 | |||||
Surge current resistance (wave 8/20) | A | 3000 A | ||||
Mechanical features | Housing | Insulation group I - II, RAL 7035 | ||||
Toggle | Insulation group II, RAL 5017 | |||||
Test button | Insulation group II, RAL 2000 | |||||
Contact position indication | Green / Red window | |||||
Earth fault trip indication | White window | |||||
Electrical life | Operations | 4000 cycles | ||||
Mechanical life | Operations | 10000 cycles | ||||
Protection degree acc. to EN 60529 | Housing | IP4X | ||||
Terminals | IP2X | |||||
Shock resistance acc. to IEC/EN 60068-2-27 | 25g - 2 shocks - 13ms | |||||
Vibration resistance acc. to IEC/EN 60068-2-6 | 0.1 mm or 1 g - 20 cycles at 5…150…5 Hz | |||||
Environmental conditions (damp heat) acc. to IEC/EN 60068-2-30 | °C/RH | 28 cycles with 55°C/90-96% and 25°C/95-100% | ||||
Reference temperature for setting of thermal element | °C | 30 °C | ||||
Ambient temperature (with daily average ≤ +35 °C) | °C | -25… +40 °C | ||||
Storage temperature | °C | -40… +70 °C |
Installation | Terminal type | Twin-purpose terminal (lift / open-mouthed) | ||||
Terminal size for cables | bottom / top | mm² | 25/35 mm² | |||
Terminal size for PIN busbar | bottom / top | mm² | 10/16 mm² | |||
Terminal size for FORK busbar | bottom / top | mm² | M6 - 10/16 mm² | |||
Solid /stranded wiring | 1x 1mm² - 35mm² 2 x 1mm² - 16mm² * |
|||||
Flexible wires with or without ferrules | 1x 1mm² - 25mm² 2 x 1mm² - 10mm² * |
|||||
Tightening torque | bottom / top | 2 Nm | ||||
Stripping length of the cable | 10mm | |||||
Mounting | On DIN rail EN 60715 (35mm) by means of mounting clip |
|||||
Mounting position | Any | |||||
Connect from | Top/bottom terminals | |||||
Dimensions (H x W x D) | mm | 83 x 36 x 72 mm | 83 x 72 x 72 mm | 88 x 81 x 72 mm | ||
Weight | kg | 0.19 kg | 0.42 kg | 0.47 kg | ||
Packing | Packing A (Individual box) |
Quantity | pieces | 1 | 1 | 1 |
Dimension (H*W*D) | mm | 90*40*80 mm | 90*78*81 mm | 95*86*82 mm | ||
Weight | kg | 0.2 kg | 0.43 kg | 0.48 kg | ||
Packing B (*A) (Middle box) |
Quantity | pieces | 6 | 3 | 2 | |
Dimension (H*W*D) | mm | 255*95*91.2 mm | 242*98*89 mm | 200*90*87 mm | ||
Weight | kg | 1.3 kg | 1.3 kg | 1.3 kg | ||
Packing C (*B) (Master carton) |
Quantity | pieces | 60 | 30 | 20 | |
Dimension (H*W*D) | mm | 510*275*200 mm | 520*255*200 mm | 470*210*190 mm | ||
Weight | kg | 14.5 kg | 14.5 kg | 11 kg | ||
Combination with auxiliary elements |
Auxiliary contact | Yes | Yes | NA (yes) | ||
Allarm contact | Yes | Yes | NA (yes) | |||
Shunt trip | NA (yes) | NA (yes) | NA (yes) | |||
Auxiliary contact for bottom fitting | NA (yes) | NA (yes) | NA (yes) | |||
Undervoltage release | NA (yes) | NA (yes) | NA (yes) | |||
Overvoltage release | NA (yes) | NA (yes) | NA (yes) | |||
Motor operating device | NA (yes) | NA (yes) | NA (yes) |