Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Electromagnetic |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Type | HSL1-2A | HSL1-4A | |||
Standards | IEC/EN 61008-1, IEC/EN 61008-2-1; | ||||
Certificate | SEMKO, CB, CE, UKCA, RoHS | ||||
Country of origin | CHINA | ||||
Electrical features | Type (wave form of the earth leakage sensed) | Type A Type AC |
|||
Number of poles | 1P+N | 3P+N | |||
Rated current | In | A | 25, 32, 40, 63, 80, 100 A | 25, 32, 40, 63, 80, 100 A | |
Rated sensitivity | IΔn | mA | 30, 100, 300 mA | 30, 100, 300 mA | |
Rated voltage | Ue | V | 220/230/240 V | 380/400/415 V | |
Operating time | Type A / Type AC | Instantaneous | |||
Insulation voltage | Ui | V | 500V AC | ||
Overvoltage category | III | ||||
Pollution degree | 2 | ||||
Operating voltage of circuit test | V | 187 - 264 V | 230 - 485 V | ||
Rated frequency | Hz | 50/60 Hz | |||
Rated breaking capacity acc. to IEC/EN 61008-1 | Inc | A | 10,000 A | ||
Rated residual making and breaking capacity acc.to IEC/EN 61008-1 |
IΔm | A | 800 A | ||
Rated impulse withstand voltage (1.2/50μs) | Uimp | kV | 4 kV |
Mechanical features | Housing | Insulation group I - II, RAL 7035 | |||
Toggle | Insulation group II, RAL 5017 | ||||
Test button | Insulation group II, RAL 2000 | ||||
Contact position indication | Green / Red window | ||||
Earth fault trip indication | White window | ||||
Electrical life | Operations | 4000 cycles | |||
Mechanical life | Operations | 10000 cycles | |||
Protection degree acc. to EN 60529 | Housing | IP4X | |||
Terminals | IP2X | ||||
Shock resistance acc. to IEC/EN 60068-2-27 | 25g - 2 shocks - 13ms | ||||
Vibration resistance acc. to IEC/EN 60068-2-6 | 0.1 mm or 1 g - 20 cycles at 5…150…5 Hz | ||||
Environmental conditions (damp heat) acc. to IEC/EN 60068-2-30 | °C/RH | 28 cycles with 55°C/90-96% and 25°C/95-100% | |||
Reference temperature for setting of thermal element | °C | 30 °C | |||
Ambient temperature (with daily average ≤ +35 °C) | °C | -25… +40 °C | |||
Storage temperature | °C | -40… +70 °C | |||
Installation | Terminal type | Twin-purpose terminal (lift / open-mouthed) | |||
Terminal size for cables | bottom / top | mm² | 25/35 mm² | ||
Terminal size for PIN busbar | bottom / top | mm² | 10/16 mm² | ||
Solid /stranded wiring | 1x 1mm² - 35mm² 2 x 1mm² - 16mm² * |
||||
Flexible wires with or without ferrules | 1x 1mm² - 25mm² 2 x 1mm² - 10mm² * |
||||
Tightening torque | bottom / top | 2 Nm | |||
Stripping length of the cable | 10mm | ||||
Mounting | On DIN rail EN 60715 (35mm) by means of mounting clip |
||||
Mounting position | Any | ||||
Connect from | Top/bottom terminals | ||||
Dimensions (H x W x D) | mm | 90 x 36 x 72 mm | 90 x 72 x 72 mm | ||
Weight | kg | 0.18 kg | 0.31 kg | ||
Packing | Packing A (Individual box) |
Quantity | pieces | 1 | 1 |
Dimension (H*W*D) | mm | 90*37*78 mm | 88*75*80 mm | ||
Weight | kg | 0.2 kg | 0.33 kg | ||
Packing B (*A) (Master carton) |
Quantity | pieces | 60 | 30 | |
Dimension (H*W*D) | mm | 470*262*177 mm | 400*280*185 mm | ||
Weight | kg | 12.48 kg | 10.42 kg | ||
Combination with auxiliary elements |
Auxiliary contact | NA (yes) | NA (yes) | ||
Allarm contact | NA (yes) | NA (yes) | |||
Shunt trip | NA (yes) | NA (yes) | |||
Auxiliary contact for bottom fitting | NA (yes) | NA (yes) | |||
Undervoltage release | NA (yes) | NA (yes) | |||
Overvoltage release | NA (yes) | NA (yes) | |||
Motor operating device | NA (yes) | NA (yes) |